|
POSITIVE PRESSURE
FIRE RATED DOOR ASSEMBLIES
Now that the codes requiring doors to be
tested to positive pressure test methods are being adopted and enforced
throughout much of the country, it is probably a good time to review the
changes and practices being utilized in the wood door industry. When UBC
1997 (the Uniform Building Code) was in the initial stages of being
implemented, there was a lot of confusion and uncertainty concerning how the
industry was going to comply with the new requirement. Most of the smoke has
now settled, and a much clearer picture of what is required has emerged.
Parts of the country have yet to require positive pressure rated doors, so I
will start with the basics and progress into how these changes are currently
being implemented.
What Is a Positive Pressure Door?
A positive pressure fire door is a door that has successfully been tested to
the new test methods [UBC 7-2-97 and UL-10C (Underwriters Laboratories)] for
life safety concerns. These tests were designed to be more consistent with
real world fire conditions than the old neutral/negative pressure test. The
positive pressure test, which takes place in a furnace, establishes a
neutral pressure plane 40" above the bottom of the door. Above the neutral
pressure plane, the pressure in the furnace is greater than outside of the
furnace, causing hot gases and flames to flow around the door. Below the
neutral pressure plane, cool air from outside the furnace flows into the
furnace. (See detail of furnace on next page.) The UBC 7-2-97 test method is
included in the UBC 1997 code.
|
 |
The Building Codes and Positive Pressure
The International Conference of Building Officials (ICBO) changed its code,
the UBC, in 1997 to require fire doors to be tested in a positive pressure
environment to reflect conditions that occur in actual fires. In 2000, ICBO
joined with two other major code groups, BOCA and SBCCI (Building Officials
and Code Administrators, and Southern Building Code Congress International),
and formed a new set of codes: the IBC (International Building Code). The
IBC also requires doors to be tested to positive pressure. By 2003, a total
of 35 states will have adopted the IBC. Positive pressure doors will be the
typical fire door required throughout the United States in the future.
Categories of Positive Pressure Openings
Companies have developed different constructions and systems to make
openings that comply with positive pressure. Due to the possible variations,
Intertek Testing Services/Warnock Hersey (ITS/WH) and Underwriters
Laboratories (UL) have developed a category system to simplify and
standardize the different types of products that openings can consist of to
be in compliance with the new codes. It is a system that breaks doors and
components into categories.
Category "A" doors – fire doors that do not require the addition of
other components such as edge seals to comply with positive pressure
requirements. This can be accomplished by intumescents being incorporated in
the door construction, or it may not be needed at all.
Category "B" doors – fire doors that require the addition of an edge
seal to comply with positive pressure requirements. Edge seals could be
intumescent and/or gasketing— the manufacturer has approval for. The edge
seals are typically added to the frame.
Category "C" frames – fire door frames that play an integral part in
the door assembly in complying with positive pressure requirements. An
example would be a frame with built-in intumescents.
Category "D" door/frame assemblies – doors and frames that together
are labeled as an assembly.
Category "F" light kits – light kits that have been evaluated for
positive pressure.
Category "G" edge sealing systems – edge seals that are
surface-applied to frames or doors. These seals may or may not have an
effect on meeting the leakage requirements for the smoke ("S") rating.
Category "H" smoke and draft control gasketing – gasketing materials
that are added to a door assembly to comply with the requirements of UBC
7-2-97 Part II.
Category "J" gaskets – gasketing materials that are added to a door
assembly for purposes other than Category "G" edge seals and Category "H"
smoke and draft control gaskets. They are used for purposes such as
weather-stripping and for sound control. They meet the requirements for
positive pressure tests and can be used on these assemblies.
There can be some overlapping when you use the category system, as the
following example illustrates: You have an acoustical door that needs to be
20-minute fire rated. For the acoustics, you use Category "J" gaskets. The
"J" gaskets are also approved Category "G" edge sealing systems for
20-minute doors to qualify the door as a Category "B" door. In this case,
the edge seals qualify as both Category "G" and "J" for use on a Category
"B" door.
Smoke Control Doors
As previously discussed, in the new codes, there are two completely
different parts that need to be addressed. The first part, UBC 7-2-97 Part
I, is concerned with positive pressure; the second part, 7-2-97 Part II, is
concerned with smoke control. Smoke control doors require Category "H"
gasketing to be in compliance with UBC 7-2-97 Part I. ITS/WH and UL require
smoke control doors to have an "S" on their labels to signify that the door
can comply with the smoke control requirement if installed per the
manufacturer's installation requirements. This "S" on the label has caused
some people to refer in specifications to an "S-Labeled" door. A door can
have a separate S-label on it, but the "S" is typically incorporated as part
of the fire label.
Who Is Responsible for Determining if Openings Comply?
The ultimate authority that determines if an opening meets the code
requirements is the code official or AHJ (Authority Having Jurisdiction).
Since there are many varying combinations of products that can be put
together to be in compliance with the codes, we need to give the AHJ the
tools to determine whether an opening is compliant or not. ITS/WH and UL
require all positive pressure labels to have printed on them "See
installation instructions." Each order that door manufacturers ship with
positive pressure doors is required to be accompanied by a packet of
installation instructions. It is important that these instructions are
passed along so that they are available when the AHJ makes its inspection.
How Do I Know if a Project Is for Positive Pressure or Not?
With all the changes that are taking place, specifications for jobs will
probably be confusing at times. Following are some key phrases to look for
when reading specifications.
1. Key Phrases Indicating Positive Pressure
A. UBC 7-2-1997 Code
B. IBC 2000 Code
C. UL-10C Fire Test
D. ASTM 2074-00 Fire Test
E. After 5 minutes into the test, the neutral pressure plane should be at
40"
F. Shall meet positive pressure requirements
G. Intumescent seals – a phrase that implies positive pressure
2. Key Phrases Indicating Negative (Neutral) Pressure
A. UL-10B Fire Tested
B. UBC 7-2-1994 Code
C. UBC 43-2 UBC Fire Test
D. Tested at atmospheric pressure
E. ASTM E-152 Test Method
3. Phrases that Don' Indicate Positive or Negative Pressure
A. NFPA-101 Life Safety Code
B. NFPA-105 Smoke and Draft Control Document
C. NFPA-252 Fire Test Method, which gives the option to be positive or
negative
D. UBC with no date given could be either positive or negative
E. UL-1784 Air Leakage Test for Door Assemblies
F. NFPA-80 Installation Standard for Fire Doors and Windows
Temperature Rise Requirements
The new codes also have temperature rise requirements. Doors are available
in three classifications: above 650° F, 450° F and 250° F. The lower the
number, the better the door. A maximum temperature rise of 450° F is
required for exit enclosures. The temperature rise designation must be on
the fire label. Wood doors are very good insulators; on 60- and 90-minute
doors, you will typically see a designation that states "Maximum 250 Degrees
F after 30 Minutes." Below is a description of how temperature rise levels
are derived.
-
Before the fire test begins, the temperature on the non
fire-side of the door is measured.
-
After 30 minutes into the test, the temperature is
measured again.
-
The difference between the two measurements is the
temperature rise.
-
Wood doors typically have less than a 250° F
temperature rise.
-
As a 250° F rise is less than a 450° F rise, it exceeds
the standard.
-
Typically, on 60- and 90-minute wood doors, a 250° F
temperature rise is designated right on the fire label.
-
The exceptions to this are doors with louvers and doors
with non-insulated glass over 100 square inches.
Labeling Requirements
Here is a recap of the new information that you will see on positive
pressure fire labels.
-
You will see "See Installation Instructions."
-
You will see an "S" on the label. This designates that
the door can be a smoke control door, if the installation instructions are
followed. Door manufacturers are allowed to put an "S" on all of
their labels, but the door does not become a smoke control door until the
installation instructions have been followed.
-
You will see on 60- and 90-minute labels either a 250°
F or 450° F maximum temperature rise designation. If the door does not
meet the 450° F temperature rise rating, the designation will read " Rise
in Excess of 650F Degrees."
-
Positive pressure labels will also reference the new
code UBC 7-2- 1997 and could reference the positive pressure test methods
UL 10C.
There are two basic ways in which the doors can supply this new information.
One way is on a full label, and the other way is on a half tab that is put
on in addition to a current negative pressure label. Both are shown above.
Changes typically make people uncomfortable until they become familiar with
the new ideas. The new codes can be confusing, but with time and education,
it will not be too long before this new way will be accepted as " the way we do
things." There have been some positive outcomes that have come from the
changes already. With the use of materials that expand when heated (intumescents),
the wood door industry has approvals it did not have in the past— concealed
vertical rods with no metal edges, 90-minute double egress openings,
concealed closers, and less bottom rod applications (available now because
of auxiliary fire latches, sometimes called " poppers" Most importantly, however,
the biggest positive is an improvement in life safety.

16 Park Avenue, Staten Island, NY 10302
Copyright 2008 - All rights reserved
ENJO Architectural Millwork reserves the
right to change product details
without notice.
www.enjo.com
|
|